6 evaporator temperature display, 7 condenser temperature display – EVCO EVXV815P7 Installer manual User Manual

Page 18

Advertising
background image

EVCO S.p.A.

EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 18 of 66

Operate as follows to exit the procedure:

5.

Press and release the BLAST CHILLING key or do not operate for 15 s: the display will show “Pb1” again.

6.

Press and release the UP or DOWN key until the display shows the magnitude indicated in paragraph 5.3 "The

display" or do not operate for 60 s.

5.5

Display of the temperature detected by the needle

probe

Operate as follows:

1.

Make sure that the keyboard is not locked and that no procedure is in progress.

2.

Hold the DOWN key for 1 s: the display will show the first label available.

3.

Press and release the UP or DOWN key to select “Pb2”.

4.

Press and release the BLAST CHILLING key: the display will show the temperature detected by the needle

probe.

Operate as follows to exit the procedure:

5.

Press and release the BLAST CHILLING key or do not operate for 15 s: the display will show “Pb2” again.

6.

Press and release the UP or DOWN key until the display shows the magnitude indicated in paragraph 5.3 "The

display" or do not operate for 60 s.

If the needle probe is not enabled, i.e. if parameter P3 is set at 0, the “Pb2“ label will not be displayed.

5.6

Evaporator temperature display

Operate as follows:

1.

Make sure that the keyboard is not locked and that no procedure is in progress.

2.

Hold the DOWN key for 1 s: the display will show the first label available.

3.

Press and release the UP or DOWN key to select “Pb3”.

4.

Press and release the BLAST CHILLING key: the display will show the evaporator temperature.

Operate as follows to exit the procedure:

5.

Press and release the BLAST CHILLING key or do not operate for 15 s: the display will show “Pb3” again.

6.

Press and release the UP or DOWN key until the display shows the magnitude indicated in paragraph 5.3 "The

display" or do not operate for 60 s.

If the evaporator probe is not enabled, i.e. if parameter P4 is set at 0, the “Pb3“ label will not be displayed.

5.7

Condenser temperature display

Operate as follows:

1.

Make sure that the keyboard is not locked and that no procedure is in progress.

2.

Hold the DOWN key for 1 s: the display will show the first label available.

3.

Press and release the UP or DOWN key to select “Pb4”.

4.

Press and release the BLAST CHILLING key: the display will show the condenser temperature.

Operate as follows to exit the procedure:

5.

Press and release the BLAST CHILLING key or do not operate for 15 s: the display will show “Pb4” again.

6.

Press and release the UP or DOWN key until the display shows the magnitude indicated in paragraph 5.3 "The

display" or do not operate for 60 s.

If the condenser probe is not enabled, i.e. if parameter P5 is set at 0, the “Pb4“ label will not be displayed.