11

ALARMS

11.1

Alarms

The following table illustrates the meaning of the alarm codes.

Code

Meaning

tiME

Temperature-controlled blast chilling or deep freezing not concluded within maximum duration alarm

(HACCP alarm).

Solutions:

-

check the value of parameters r5 and r6 and AA.

Main consequences:

-

the device will memorise the alarm.

AL

Minimum temperature alarm.

Solutions:

-

check the temperature of the cabinet

-

check the value of parameters A1 and A2.

Main consequences:

-

the device will continue to operate normally.

AH

Maximum temperature alarm (HACCP alarm).

Solutions:

-

check the temperature of the cabinet

-

check the value of parameters A4 and A5.

Main consequences:

-

the device will memorise the alarm.

id

Door open alarm

Solutions:

-

check the door conditions

-

check the value of parameters i0 and i1.

Main consequences:

-

the effect established with parameter i0.

HP

High pressure alarm.

Solutions:

-

check the conditions of the high pressure input

-

check the value of parameters i5 and i6.

Main consequences:

-

the effect established with parameter i5.