EVCO EVXV815P7 Installer manual User Manual

Page 42

Advertising
background image

EVCO S.p.A.

EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 42 of 66

F2

0

3

- - - -

3

3

evaporator fan activity during storage

0 = off

1 = on

2 = parallel to the compressor; also see

parameter F9

3 = on; also see parameter F1

F3

0

15

min

2

2

duration of evaporator fan standstill (the

compressor can be on during evaporator fan

standstill, the defrosting output will remain

deactivated and the evaporator fan will

remain off)

F8

0.1

15.0

°C/°F (1)

2.0

2.0

F1, F16 and F17 parameters differential

F9

0

240

s

0

0

evaporator

fan

switch-off

delay

from

compressor switch off (only if parameter F0

and/or parameter F2 are set at 2)

F11

0.0

99.0

°C/°F (1)

not

present

15.0

condenser temperature above which the

condenser fan is switched on (intended as

“F11 + differential and on condition that the

compressor is on); also see parameter F12

(4) (12) (13)

F12

0

240

s

not

present

30

condenser

fan

switch-off

delay

from

compressor switch-off

F15

0

240

s

15

15

evaporator fan delay from door closure, i.e.

from the deactivation of the door micro switch

input

F16

-50.0

99.0

°C/°F (1)

20.0

20.0

evaporator temperature above which the

evaporator fan is off during pre-cooling, blast

chilling and deep freezing (only if parameter

F0 is set at 1); also see parameter F8 (11)