EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 44 of 66

i5

0

1

- - - -

1

1

effect caused by the activation of the high

pressure input

0 = no effect

1 = the compressor and the evaporator fan

will be off and the condenser fan will

be on. On expiry of the time

established with parameter i7, the

display will show the flashing “HP

code and the buzzer will be activated

(until the input is deactivated)

i6

0

1

- - - -

0

0

type of high pressure input 1

0 = normally open (input active with closed

contact)

1 = normally closed (input active with open

contact)

i7

-1

240

s

5

5

high pressure alarm signalling delay (“HP

code)

-1 = the alarm will not be signalled

Par.

Min.

Max.

Unit

EVXV802

EVXV812

EVXV805

EVXV815

Digital outputs

u0

0

1

- - - -

1

not

present

utility managed by the output K2 (16)

0 = defrosting (in this case, the “d”

parameters will assume significance)

1 = evaporator fan (in this case, the “F”

parameters will assume significance)

u1

0

1

- - - -

not

present

0

utility managed by the output K4 (16)

0 = door

resistances

(in

this

case,

parameter u5 will assume significance)

1 = condenser fan (in this case, the P5,

F11 and F12 parameters will assume

significance)

u2

0

1

- - - -

not

present

0

enabling of cabinet light switch-on/off in

manual mode during "stand-by" status (17)

1 = yes

u5

-50.0

99.0

°C/°F (1)

not

present

20.0

cabinet temperature over which the door

resistances are off (4)