4 deep freezing and storage – EVCO EVXV815P7 Installer manual User Manual

Page 24

Advertising
background image

EVCO S.p.A.

EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 24 of 66

To display the cabinet temperature, press and release the BLAST CHILLING key; to restore the normal display, press

and release the BLAST CHILLING key again or do not operate for 15 s.

If the temperature detected by the needle probe reaches the blast chilling end temperature within the maximum blast

chilling duration, it means that blast chilling has been completed successfully, the device will automatically pass to

storage and the buzzer will be activated for the period of time established with parameter AA.

Press and release a key to silence the buzzer.

During storage, the display shows the temperature detected by the cabinet and the LED is on.

Parameter r10 establishes the work set-point during storage.

If the temperature detected by the needle probe does not reach the blast chilling end temperature within the

maximum blast chilling duration, blast chilling will not be completed successfully but will continue, the

LED will

flash and the buzzer will be activated.

Press and release a key to restore normal display and to silence the buzzer.

To display the cabinet temperature, press and release the BLAST CHILLING key; to restore the normal display, press

and release the BLAST CHILLING key again or do not operate for 15 s.

When the temperature detected by the needle probe reaches the blast chilling end temperature, the device

automatically passes to storage in the same way as illustrated previously.

6.4

Deep freezing and storage

The temperature-controlled deep freezing and storage cycle is divided into the following two phases:

-

deep freezing

-

storage

On conclusion of a phase, the device passes automatically to the next.

Operate as indicated to start the cycle:

1.

Make sure the device is in the "on" status.

2.

Make sure that the keyboard is not locked and that no procedure is in progress.

3.

Press and release the DEEP FREEZING key: the

LED, the

LED, the HARD LED and the

LED will

flash.

If parameter r21 has value 1, press and release the DEEP FREEZING key to start the cycle with timed-control:

the

LED, the

LED, the HARD LED and the

LED will flash and the

LED will switch off (press and

release the DEEP FREEZING key again to start the cycle with temperature-control).

4.1

If parameter r19 is set at 0, the display will show the work set-point during deep freezing; this value can also

be set via parameter r8.

If parameter r21 has value 1 and it has been decided to start the cycle with timed-control, the display will show

the duration of time-controlled deep freezing; this value can also be set via parameter r2.

4.2

If parameter r19 is set at 1, the display will show the deep freezing end temperature; this value can also be set

via parameter r4.

If parameter r21 has value 1 and it has been decided to start the cycle with timed-control, the display will show

the duration of time-controlled deep freezing; this value can also be set via parameter r2.

4.3

Press and release the UP or DOWN key within 15 s to modify the parameter value:

5.

Press and release the START/STOP key: the

LED, the

LED and the HARD LED will remain permanently

on and the test to verify the correct insertion of the needle probe will be started; see paragraph 6.7 " Test for

verification of the correct insertion of the needle probe".

If parameter r21 has value 1 and it has been decided to start the cycle with timed-control, also the

will

remain permanently on and the cycle will be started with timed-control.

5.1

If the test is completed successfully, the cycle will be started.

The maximum deep freezing duration count is started on condition that the temperature detected by the

needle probe is below that established with parameter r15.

5.2

If the test is not completed successfully, the cycle will be started with timed-control.