EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 38 of 66

C3

0

240

s

0

0

compressor switch-on minimum duration

C4

0

240

min

10

10

duration of compressor switch-off during the

cabinet probe error (“Pr1” code) that occurs

during storage; see also parameter C5

C5

0

240

min

10

10

duration of compressor switch-on during the

cabinet probe error (“Pr1” code) that occurs

during post blast chilling storage; also see

parameter C4

C6

0

199.0

°C/°F (1)

80.0

80.0

condenser temperature above which the

blocked overheated condenser alarm is

activated (“COH” code)

C7

0

199.0

°C/°F (1)

90.0

90.0

condenser temperature above which the

blocked compressor alarm is activated (“CSd

code)

C8

0

15

min

1

1

blocked compressor alarm delay (“CSd” code)

(5)

C9

0

240

min

30

30

duration of compressor switch-on during the

cabinet probe error (“Pr1” code) that occurs

during post deep freezing storage; also see

parameter C4

Par.

Min.

Max.

Unit

EVXV802

EVXV812

EVXV805

EVXV815

Defrosting (6)

d0

0

99

h

8

8

defrosting interval (7)

0 = defrosting will never be activated at

intervals