EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 40 of 66

d7

0

15

min

2

2

dripping duration (the compressor and the

evaporator fan remain off during dripping and

the defrosting output will be deactivated)

d15

0

99

min

0

0

minimum duration of compressor switch-on

on activation of defrosting so these can be

activated (only if parameter d1 is set at 1) (8)

d16

0

99

min

0

0

duration of pre-dripping (only if parameter d1

is set at 1; the compressor and evaporator

fan will be off during pre-dripping and the

defrosting output will remain activated)

Par.

Min.

Max.

Unit

EVXV802

EVXV812

EVXV805

EVXV815

Temperature alarms (9) (10)

A1

0.0

99.0

°C/°F (1)

10.0

10.0

cabinet

temperature

below

which

the

minimum temperature alarm is activated

(relative to the work set-point, i.e. “r10 - A1”

during post blast chilling storage and “r11 -

A1” during post deep freezing storage; (“AL

code); also see parameter A11 (4)

A2

0

1

- - - -

1

1

enabling of minimum temperature alarm

(“AL” code)

1 = yes

A4

0.0

99.0

°C/°F (1)

10.0

10.0

cabinet

temperature

above

which

the

maximum temperature alarm is activated

(relative to the work set-point, i.e. “r10 +A4”

during post blast chilling storage and “r11

+A4” during post deep freezing storage;

(“AH” code); also see parameter A11 (4)

A5

0

1

- - - -

1

1

enabling of maximum temperature alarm

(“AH” code)

1 = yes

A7

0

240

min

15

15

temperature alarm delay (“AL” code and

AH” code)