8.6 ProfiNet Option

Indicators which are equipped with the ProfiNet option can be connected to a PLC bus as described below.

Weight data update rate

40 ms

Response time on entries

5 ms to 25 ms

8.6.1 Electrical Connections

ProfiNet Interface:

1. Network Status LED

2. Module Status LED

3. Link/Activity LED

4. Ethernet Connector (100 Mbit/s, full-duplex)

MS Module Status LED

LED State

Description

Comment

Off

No power or not initialized

No power or ProfiNet module is in initialization state

Green

Initialized

Green, 1 flash

Initialized, diagnostic event(s) present

Diagnostic is active

Green, 2 flashes

Blink

Service tool to identify the node on the network

Red

Exception error

There is an exception error

Red, 1 flash

Configuration error

Check EDS configuration

Red, 2 flashes

IP address error

IP address not set

Red, 3 flashes

Station name error

Station name not set

Red, 4 flashes

Internal module error

Re-energize the instrument. If seen again, change module

LINK/Activity LED

LED State

Description

Comment

Off

No Link

No link, no communication present

Green

Link

Ethernet link established, no communication present

Green, flickering

Activity

Ethernet link established, communication present

NS Network Status LED

LED State

Description

Comment

Off

Not online /No power

Check power and cable

Green

On-line (RUN)

-

Green, flashing

On-line (STOP)

-

8.6.2 Setup

[0--] Interface Block

[03-] ProfiNet

[036 X ] Data Format

0 : Signed 32 bit integer

1 : Signed 32 bit floating point

There are 7 setup parameters for ProfiNet network:

DHCP

Enabled Dynamic Host Configuration Protocol automates network parameters. Default is „Disable‟.

IP Address

If DHCP is disabled, define IP address manually. Default is „192.168.16.250‟

Subnet Mask

If D

HCP is disabled, define subnet mask manually. Default is „255.255.255.0‟.

Gateway

If DHCP is disabled, define default gateway manually. Default is „192.168.16.254‟.

Primary DNS

If DHCP is disabled, define primary DNS manually. Default is „208.67.222.222‟.

Secondary DNS

If DHCP is disabled, define secondary DNS manually. Default is „208.67.220.220‟.

Host Name

Enter a unique host name to the instrument. Default is „ ‟

The ProfiNet communication will be configured by the EtherX PC software. EtherX can be installed from the
Flintec Product CD-ROM. The EDS file is available on a CD which is supplied together with the instrument.
After the setup of these parameters and the hardware connection as described above, the data interface can
be used as described in Appendix 4.

Important hint: During the setup the ProfiNet output (weight value and status bits) will not be updated.

8.6.3 Data Structure

See Appendix 4.