2 threshold and control, Threshold and control – ADLINK PXES-2590 User Manual

Page 40

Advertising
background image

30

System

Management

Version Info

Displays the current firmware version and 10MHz clock source.

3.2.2

Threshold and Control

Provides operational and threshold settings for the PXES-2590,
including target temperature, fan mode, and threshold settings for
DC voltage, temperature, and cooling fan speeds.

Target Temperature

Fans run at different speeds based on the monitored tempera-
ture, when the Fan switch on the rear panel is set to AUTO.

Target Temp indicates the temperature when the fans are at

100%. Using the default 50°C as an example, fans run at 40%
when all temperature readings are less than 25°C, and begin
rampup when any reading exceeds 25°C. The fans run 100%
speed if any temperature reading exceeds 50°C (Target Tem-
perature). Target temperature setting parameters are as
shown.

Advertising