Monitoring/Control Functions

53

PXES-2590

Use the SMB write word to write this word data:

Data format is as follows::

*Write Temperature Alarm Threshold (command 0xBE)

Writes the Temperature Alarm Threshold.

Use the SMB write word to write this word data:

Data format is as follows:

SMB

Dir

Offset

Value

Description

Write word

>

0

SA

Slave address

>

1

0xBC

Command code

>

2

0-255

Low byte data

>

3

0-255

High byte data

Bit

Description

15..0

Fan Speed Alarm Threshold. Unsigned 16-bit data,
the LSB is 1rpm. If any of the fan speed is lower
than this threshold, the MCU triggers a fan speed
alarm. The threshold range is between 1 and 10000

SMB

Dir

Offset

Value

Description

Write word

>

0

SA

Slave address

>

1

0xBE

Command code

>

2

0-255

Low byte data

>

3

0-255

High byte data

Bit

Description

7..0

Temperature Alarm Threshold. Unsigned 8-bit data, the
LSB is 1°C. If MCU detects any of the backplane
temperature (Temperature 0~7) is higher than the
threshold, the MCU triggers a temperature alarm. The
threshold range is between 0 and 110

15..8

Reserved.