3 chassis status, Chassis status – ADLINK PXES-2590 User Manual

Page 42

Advertising
background image

32

System

Management

Fan Speed

Auto/Full status of the PXES-2590 is shown here, Auto is dis-

played when the cooling fans are set to auto mode and Full
when the fans are set to run full speed. Selection of Auto or
Full values and clicking Set directly changes cooling fan mode.

Alarm Threshold

Active alarm threshold settings are shown, including DC volt-

age, temperature, and fan speeds. The updated threshold set-
ting can also be set here, by entering the desired value and
clicking Set Threshold Settings.

3.2.3

Chassis Status

DC Voltage

The monitored 5V AUX, 3.3V, 5V, 12V, and -12V power rail

readings are shown here. The status shows as normal when
the readings are within the threshold range, and abnormal
when the readings exceed the threshold range.

Chassis Temperature

Temperature sensors T1 to T5 located on the backplane from

left to right provide status, showing as normal when under the
threshold value (70

°

C in the figure), and abnormal when

exceeding the threshold value.

Fan Speed

Monitored readings of the three cooling fans appear here. Sta-
tus shows as normal when readings exceed threshold value
(800 RPM in the figure), and abnormal when the readings fall
below the threshold value.