Chapter 2: Installation and Wiring

2-9

User’s Manual Pub. 0300272-01 Rev. A.0

Noise Prevention

Route field wiring away from any other wiring and as far as possible from
sources of electrical noise, such as motors, transformers, contactors, and AC
devices. As a general rule allow at least 15.2 cm (6 in.) of separation for every
120 V of power.

Routing field wiring in a grounded conduit can reduce electrical noise.

If field wiring must cross AC or power cables, ensure that they cross at right
angles.

If noise persists for a device, try grounding the opposite end of the cable shield
or ground both ends of the shield.

2.5.1 Wiring Diagram

Refer to the following wiring diagrams for field wiring connections.

Table 2-1 (2 Channel Terminal Block Pinout)

RTB

Pin#

Usage

RTB

Pin#

Usage

0

Isolated 0ut0+

1

Isolated 0ut1+

2

Isolated Out0-

3

Isolated Out1-

4

Unused

5

Unused

6

Chassis GND

(FGND)

7

Chassis GND

(FGND)

Figure 2-1 (OE2CIH Wiring Diagram)