Channel status bits, Module status, Channel hard fault – Spectrum Controls 1734sc-OE2CIH User Manual

Page 48

Advertising
background image

4-12

Chapter 4: OE2CIH and HART

User’s Manual Pub. 0300272-01 Rev. A.0

Table 4-8 Input-Only Assembly

Instance:

ID:

Description:

Total Size:

100

3

Channel Status Only

12 Bytes RSL 5 K (DeviceNet 8 bytes)

Bit

15

14

13 12

11

10

09

08 07

06

05

04

03

02

01

00

Analog
data 4
bytes
0Ч00-0Ч03

Module Status - UINT

High Byte–Channel 1 Status

Low Byte–Channel 0 Status

HF

Bits

13-14

not

used

OC

HCA LCA CM CF HF

Bits 05-

06 not

used

OC HCA LCA CM CF

Channel Status Bits

CF = Channel Fault status; 0 = no error; 1 = any fault (LCA, HCA, OC)

CM = Calibration Mode; 0 = no calibration taking place; 1 = calibration in
process

LCA = Low Clamp Alarm; 0 = no alarm; 1 = Low alarm equal to or less than
Low Limit user value.

HCA = High Clamp Alarm; 0 = no alarm; 1 = High alarm equal to or greater
than High Limit user value.

OC = Open Circuit; 0 = no error; 1 = open circuit

HF = Hard Fault; 0 = no fault; 1 = fault

Module Status

0 = Module OK

1 = Watchdog Fault

2 = Channel Hard Fault

3 = Bad or No Configuration

NOTE

The above status codes are in priority order where multiple conditions
may exist.

Channel Hard Fault

In the case where one of the HART modem CPUs cannot be communicated with, the
channel is placed in a Hard Fault Mode. The HF bit is set for that channel and the Module
Status is set to 2. The HART modem CPU is held in reset until the module is power-
cycled. This action may or may not disable the output since the reset line runs through the
same isolation IC as TX and RX. The channel status LED is set to solid Red while the
Module Status LED is set to flashing Red. The other channel is allowed to operate
normally.