6 devicenet object, 7 assembly object, 6 devicenet object -6 – Spectrum Controls 1734sc-OE2CIH User Manual

Page 42: 7 assembly object -6

Advertising
background image

4-6

Chapter 4: OE2CIH and HART

User’s Manual Pub. 0300272-01 Rev. A.0

4.2.6 DeviceNet Object

This object class configures port attributes such as baud rate and MAC ID.

Table 4-4 Device Net Object

Class Code:

0×03

Instances:

#1

Class Attributes:

None

Class Services:

None

Instance Attributes:

Attr

Name (Data Type) Value

G/S

Description

1

MAC ID (USINT)

0-63

G

The current MAC ID

2

Baud (USINT)

3

G

Baud rate.
The baud is fixed at 1 Mbps and
cannot be changed. The official
DeviceNet specification only
supports values 0 to 2 but since this
module uses a non-standard baud,
we use 3.

Instance Services:
Code

Service Name

Description

14 0×0E

Get Single

Read the value of the attribute

4.2.7 Assembly Object

The 1734sc-OE2CIH module will have one configuration assembly, two input
assemblies, and one output assembly. Multiple instances of input assemblies allow the
user to optimize system performance by limiting the produced data to that which is
needed. Input assembly options allow the user to select status only for maximum
throughput status + HART data for both channels. The AOP used for initial release will
support only the Status + All Hart Channels Instance #103.

Advertising