Table A-1 Environmental Specifications

Environmental Tests

Industry Standards

Test Level Limits

Temperature (Operating)
(Performance Criteria A)

IEC60068-2-1: (Test Ad, Operating Cold),
IEC60068-2-2: (Test Bd, Operating Dry Heat),

IEC60068-2-14: (Test Nb, Operating Thermal
Shock)

0°C to 55°C (-4°F to 131°F)
(natural convection cooling)

Temperature
(Non-operating)
(Performance Criteria B)

IEC60068-2-1:
(Test Ab, Unpackaged Non-operating Cold),

IEC60068-2-2:
(Test Bb, Unpackaged Non-operating Dry Heat),

IEC60068-2-14:
(Test Na, Unpackaged Non-operating Thermal
Shock)

-40°C to +85°C (-40°F to 185°F)

Humidity (Operating)
(Performance Criteria A)

IEC60068-2-30:
(Test Db, Unpackaged Damp Heat):

5% to 95% non-condensing

Vibration (Operating)
(Performance Criteria A)

IEC60068-2-6: (Test Fc, Operating)

10 Hz to 500 Hz, 5g

Shock (Operating)
(Performance Criteria A)

IEC60068-2-27: (Test Ea, Unpackaged Shock)

30 g, 11 ms half sine (3 mutually
perpendicular axes)

Shock (Non-operating)
(Performance Criteria B)

IEC60068-2-27: (Test Ea ,Unpackaged Shock)

50g, 11 ms half sine (3 mutually
perpendicular axes)

Radiated Emissions

CSIPR 11; Group 1, Class A

(Enclosure) Class A, 30 MHz to 1
GHz

Conducted Emissions

IEC 61000-6-4:2007

Group 1, Class A (AC Mains)
150 kHz to 30 MHz

ESD immunity
(Performance Criteria B)

IEC 61000-4-2

6 kV Indirect (Coupling Plate)

6 kV Contact Discharge (to points
of initial contact)

8 kV Air Discharge (to points of
initial contact)