5 identity object, 5 identity object -5 – Spectrum Controls 1734sc-OE2CIH User Manual

Page 41

Advertising
background image

Chapter 4: OE2CIH and HART

4-5

User’s Manual Pub. 0300272-01 Rev. A.0

All three interface types have equal priority:

The User Ladder interface uses a simplified HART interface (EZ-HART) that
only requires the user to send the HART Command number along with its data
bytes (if any) in the request data for the Init Pass-through message without
having to know how to format a real HART message. In addition the Ladder
interface has a MsgReady indicator tag in the Input table to facilitate
determining when the pass-through is complete.

The RSLogix and Asset SW interfaces require creating a complete HART
message (without preambles) as defined by the HART protocol specifications.

A pass-through message is processed with equal priority with the Device Variable scan
command (3 or 9) so the scanning on any one channel looks like this:

4.2.5 Identity Object

This object class supports the Reset service.

Table 4-3 Identity Object

Class Code:

0×01

Instance(s):

#1=entire module

Class Attributes:

None

Class Services:

None

Instance Attributes:

Instance

Attribute:

ID:

Data Type:

1734sc-OE2CIH

Notes:

Vendor ID:

1

UINT

58

Spectrum Controls
Vendor ID

Product Type:

2

UINT

10

Obsolete by ODVA

Product Code:

3

UINT

27

Revision:

4

STRUCT

(Major Rev)

USINT

1

Initial release will be
1.1

(Minor Rev)

USINT

1

Status

5

WORD

Dynamic

Serial Number

6

UDINT

Unique per module

0×1300xxxx

Product Name

7

STRUCT

(length)

USINT

30

(text)

String[28]

1734sc-OE2CIH 2 PT HART
OUTPUT

Advertising