Spectrum Controls 1734sc-OE2CIH User Manual

Page 55

Advertising
background image

Chapter 4: OE2CIH and HART

4-19

User’s Manual Pub. 0300272-01 Rev. A.0

Request Succeeded Reply
HART Read Dynamic Variables - Reply packet structure
Reply Size = 36 bytes

Offset Field

Value

Definition

0

Status

(1 byte)

Command status, 00 = SUCCESS

1

HART Command Status

(1 byte)

HART Device reply Status Byte # 1

2

HART Field Device
Status

(1 byte)

HART Device reply Status Byte # 2

3

HART Ext Device Status

(1 byte)

Status Byte returned from Cmd 9 or
0 for HART rev 5 devices

4-7

PV

(Float–4 bytes)

HART Primary variable

8-11

SV

(Float–4 bytes)

HART Secondary variable

12-15

TV

(Float–4 bytes)

HART Third variable

16-19

FV

(Float–4 bytes)

HART Fourth variable

20

PV Units

(1 byte)

Primary variable unit code

21

SV Units

(1 byte)

Secondary variable unit code

22

TV Units

(1 byte)

Third variable unit code

23

FV Units

(1 byte)

Fourth variable unit code

24

PV Assignment Code

(1 byte)

Primary variable assignment code

25

SV Assignment Code

(1 byte)

Secondary variable assignment
code

26

TV Assignment Code

(1 byte)

Third variable assignment code

27

FV Assignment Code

(1 byte)

Fourth variable assignment code

28

PV Status

(1 byte)

1 byte status from Cmd 9 (Rev 6 or
later)
OR
if Rev 5.x device:
0×C0 = Connected
0×00 = Not Connected

29

SV Status

(1 byte)

1 byte status from Cmd 9
OR if Rev 5 device:
0×C0 = Connected and Device
provides this value in CMD 3 (that
is, does not truncate)
0×00 = Not Connected

30

TV Status

(1 byte)

1 byte status from Cmd 9
OR if Rev 5 device:
0×C0 = Connected and Device
provides this value in CMD 3 (that
is, does not truncate)
0×00 = Not Connected

Advertising