Environmental Tests

Industry Standards

Test Level Limits

Radiated RF immunity
(Performance Criteria A)

IEC 61000-4-3: Level 3

10 V/M with 1 kHz sine wave 80%
AM from 80 MHz to 2000 MHz

10 V/M with 200 Hz sine wave
50% Pulse 100% AM at 900
MHz

10 V/M with 200 Hz sine wave
50% Pulse 100% AM at
1890 MHz
1 V/M with 1 kHz sine wave 80%
AM from 2000 MHz to 2700
MHz

EFT/B immunity
(Performance Criteria B)

IEC 61000-4-4

Signal Ports:

±3 kV at 5 kHz for 5 minutes

Criteria B

±2 kV at 5 kHz for 5 minutes

Criteria A

±2 kV at 5 kHz for 5 minutes
Criteria B (standard)
Power Ports:

±2 kV at 5 kHz for 5 minutes

Criteria A

±2 kV at 5 kHz for 5 minutes

Criteria B (standard)

Surge transient immunity

(Performance Criteria B)

IEC 61000-4-5

Signal Ports:

±2 kV line-earth {CM}at 2 Ω on

shielded ports

Power Ports

±2 kV CM @ 12 Ω

±1 kV DM @ 2 Ω

Conducted RF immunity
(Performance Criteria A)

IEC 61000-4-6

10 V RMS with 1 kHz sine wave
80% AM from 150 kHz to 80
MHz on signal and power ports

Magnetic field
(Performance Criteria A)

IEC 61000-4-8

30 Arms/m

AC mains voltage dips,
interruptions, and
variations

IEC 61000-4-11

Follow the 61000-4-11


Advertising