4 hart pass-through interface, 4 hart pass-through interface -4 – Spectrum Controls 1734sc-OE2CIH User Manual

Page 40

Advertising
background image

4-4

Chapter 4: OE2CIH and HART

User’s Manual Pub. 0300272-01 Rev. A.0

Commands sent at Initial Device Connection

Command:

Definition:

Comment:

2

Read Loop Current

Only sent if Cmd 9 is being used

If any information within a device is changed, the device sets its Configuration Changed
bit (bit 6 of Field Device Status byte), which is detected by the module. The module then
automatically resends the appropriate HART commands to refresh this set of data stored
in the module. The first command sent is Command

38

which will reset the

‘configuration changed’ bit in the device. An Input tag status bit in the module is used to
indicate that the device information has changed. The user may examine this bit and
resend the CIP message to get the latest device information.

Table 4-2 HART Refresh Sequence

Commands sent to refresh Device Information on Configuration Change Detected

Command:

Definition:

Comment:

38

Reset Configuration Changed Flag

Resets the Configuration Changed
Response Code, Bit 36 of the
Transmitter Status Byte. Secondary
Master devices (address 0) should not
issue this command. Primary Master
devices (address 1) should issue this
command only after the Configuration
Changed Response Code has been
detected and acted upon.

12

Read Message

See Table 4-1

13

Read Tag, Descriptor, Date

See Table 4-1

15

PV upper and lower range values

See Table 4-1

16

Read Final Assembly Number

See Table 4-1

48

Read Additional Device Status

See Table 4-1

50

Read Dynamic Variable Assignments

See Table 4-1

The following table describes the class service code and instances required to send the
Read Additional Device Status message:
The module manages different priority levels of issuing the commands to refresh the
device information data based upon whether pass-throughs are active during this time.
Asset software may be trying to configure the device, or it may be performing a
calibration sequence that needs as much bandwidth as possible

4.2.4 HART Pass-Through Interface

The module will provide a mechanism to send HART messages to a HART device on
any of the channels using the CIP unconnected messaging interface. This is called HART
pass-through because the module is just directly sending the requested HART message to
the HART device and then returning the reply to the requester.

There are three different pass-through interface types made available to support multiple
client requests for pass-through at the same time. The three types are User Ladder,
RSLogix, and Asset SW (Connects or DTM).

Advertising