Chapter 4, Section 4.1 hart features, Section 4.2 detecting hart devices – Spectrum Controls 1734sc-OE2CIH User Manual

Page 37: Chapter 4 oe2cih and hart -1, Ection, Hart, Eatures, Etecting, Evices, Chapter 4 oe2cih and hart

Advertising
background image

User’s Manual Pub. 0300272-01 Rev. A.0

Chapter 4
OE2CIH and HART

This chapter describes how to read and write HART data using the OE2CIH module. The
chapter includes the following sections:

HART features

Detecting HART devices

Auto scanning of HART dynamic variables

Supported HART CIP messages

Section 4.1
HART Features

The OE2CIH module functions as a HART master and communicates with HART
devices running HART revision 5 or greater. The OE2CIH module includes one HART
modem per channel to provide maximum acquisition speed and flexibility.

The HART transmitter and receiver conform to the HART Foundation’s physical layer
specification for a HART primary master. These specifications include AC P-P voltage
digital transmission bandwidth, analog signal bandwidth, wave shape, and a capacitive
drive.

The module performs the following HART operations:

Automatically reads the four dynamic HART variables; PV, SV, TV, and FV.

Automatically retrieves and stores HART device information, including
manufacturer’s ID device tag name, HART revision level, etc., and makes the
information available via a CIP unconnected message.

Automatically retrieves and stores extended device status using HART
Command 48. The extended status can be retrieved using an unconnected CIP
message.

Provides a HART pass-through interface using CIP unconnected messaging to
allow you or a remote client to send a HART command to a HART on any
channel.

Section 4.2
Detecting HART
Devices

Advertising