Table 4-13 Read Dynamic Variables (Service Code = 4B)

Unconnected Message

Field

Value

Definition

Message Type

CIP Generic

Service Code

0×4B

Get Device
Information

Class Name

0×035D

HART Object

Instance

1 to n

Selects channel n-1

Object Attribute

None, leave this field blank

Request Size

0

No Request Data

Reply Size

2 to 36 bytes
(2) Size when information not available
(36) Size when valid Information returned

Number of Data
bytes returned

Request Data
HART Read Dynamic Variables - Request packet structure
Request Size = 0

Offset Field

Value

Definition

No Request Data

Request Failed Reply
HART Read Dynamic Variables - Reply packet structure
Reply Size = 2

Offset

Field

Value

Definition

0

Status

34 = DR_RUNNING
(No Device or
connection process
not completed)
35 = DR_DEAD
(Channel is not HART-
enabled)

Command status

1

Pad

0

Pad byte