Request Failed Reply
HART Read Additional Status - Reply packet structure
Reply Size = 2

Offset

Field

Value

Definition

0

Status

34 = DR_RUNNING
(No Device or
connection process
not completed or re-
gathering device
info is in progress)
35 = DR_DEAD
(Channel is not HART
enabled)

Command status

1

Pad

0

Pad byte

Request Succeeded Reply
HART Read Extended Status - Reply packet structure
Instance n Reply Size = 2-28 bytes
(pad byte may be attached to end for 16 bit alignment)
Instance 0 Reply Size = 28*n
Note: Sending this message with Instance = 0 will reset the NewAdditionalStatus tag.

Offset Field

Value

Definition

0

Status

00 = SUCCESS (1 byte)

Command status

1

Count

0-25 (1 byte)

Number of Status bytes available

2-26

Additional
Status Bytes

Additional Status bytes returned by
Command 48
For Class Instance(Instance=0) if
device doesn’t return any or all 25
bytes then the remaining are set to
0.

27

Pad

0

Included if all 25 Additional Status
bytes returned or returning all n
Channels at once for Instance 0