Hart object – Spectrum Controls 1734sc-OE2CIH User Manual

Page 52

Advertising
background image

4-16

Chapter 4: OE2CIH and HART

User’s Manual Pub. 0300272-01 Rev. A.0

HART Object

CIP HART services will use a subset of the HART Object used in the modules.

Table 4-10 General CIP Message Format:

Unconnected Message Header

Field

Value

Definition

Message Type

CIP Generic

Service Code

XX–Specifies Command

Specifies Command

Class Name

0×35D

HART Object

Instance Name

0 or 1 to n where n <= number of channels
(that is first channel number=0, instance=1)

Selects channel or
all
0=All Channels
1 to 2=Chan 0 to 1

Object Attribute

None, leave this field blank

Table 4-11 1734sc-OE2CIH HART Object Services Summary:

Service: Function:
0×4B

Read Dynamic Variables

0×4C

Read Additional Device Status (Instance: 0=All, 1 to 2=channel 0 to 1)

0×4D

Ladder Get HART Device Information

0×4E

Ladder Pass through Command Request (EZ-HART) [1 QUEUE DEEP]

0×4F

Ladder Pass through Status Query (EZ-HART)

0×50

Flush Ladder Queue

0×51

Suspend Channel(s) Normal HART Acquisitions (Instance: 0=All, 1 to 2=channel 0 to 1)

0×52

Resume Channels(s) Normal HART Acquisitions (Instance: 0=All, 1 to 2=channel 0 to 1)

0×53

Set Pass through Service Rate–Not Implemented

0×54

Enable Force Command 3 for Hart 67 devices ( 1734-specific )

0×55

Disable Force Command 3 for Hart 67 devices ( 1734-specific )

0Ч56-
0Ч59

Reserve for Future Commands

0×5A

Logix Get HART Device Information

0×5B

Logix Pass through Command Request (FULL-HART) [1 QUEUES DEEP]

0×5C

Logix Pass through Status Query (FULL-HART)

0×5D

Flush Logix Queue

0×5E

Connects Get HART Device Information

0×5F

Connects Pass through Command Request (FULL-HART) [1 QUEUES DEEP]

0×60

Connects Pass through Status Query (FULL-HART)

0×61

Flush Connects Queue

0×62

Get Channel(s) Device Status (Instance: 0=All, 1-2=channel 0 to 1)

0×63

HART Message Debugging (Reserve for possible debugging feature)

Advertising