Technical data, Technical data - bcxx50 – BECKHOFF BC3150 User Manual

Page 13

Advertising
background image

Safety Instructions

Fieldbus Components

11

Technical Data

Technical Data - BCxx50

Technical data

BCxx5x

Processor

16 bit micro-controller

Diagnostic LEDs

2 x power supply, 2 x K-Bus

Configuration and programming software

TwinCAT PLC

Fieldbus
interface

BC3150

BC5150

BC5250

BC8150

-

Fieldbus

PROFIBUS DP

CANopen

DeviceNet

- Serial ADS
- KS8000 Protocol
- ModbusRTU
- ModbusASCII

-

Interfaces

Serial interface

COM1 (RS232 for configuration and programming, automatic baud rate detection
9600/19200/38400/57600 baud)

Terminal Bus (K-
Bus)

64 (255 with K-Bus extension)

Technical data

BC3150

BC5150

BC5250

BC8150

-

Digital peripheral signals

2040 inputs/outputs

Analog peripheral signals

1024 inputs/outputs

Configuration possibility

via TwinCAT or the controller

Maximum fieldbus byte
number

depending on fieldbus

Maximum number of bytes
- PLC

2048 bytes of input data, 2048 bytes of output data

Bus connection

D-sub, 9-pin

Open Style Connector, 5 pin

D-sub, 9-pin

-

Power supply (Us)

24 V

DC

(-15%/+20%) To meet the UL requirements use a 4 A fuse or a power

supply that has to satisfy NEC class 2!

Input current (Us)

60 mA + (total K-Bus current)/4

Starting current

approx. 2.5 x continuous current

K-Bus current (5 V)

maximum 1000 mA

Power contact voltage
(Up)

maximum 24 V

DC

Power contact current load
(Up)

maximum 10 A

Recommended fuse (Up)

10 A

Dielectric strength

500 V

rms

(power contact / supply voltage / fieldbus)

Weight

approx. 100 g

Dimensions (W x H x D)

approx. 44 mm x 100 mm x 68 mm