Led bus - fieldbus diagnosis – BECKHOFF BC3150 User Manual

Page 97

Advertising
background image

Safety Instructions

Fieldbus Components

95

Error
code

Error
argument

Description

Remedy

0

K-Bus data error, break
behind the Bus Coupler

Check whether the n+1 Bus Terminal is correctly connected;
replace if necessary.

4

n

Break behind Bus Terminal
n

Check whether the Bus End Terminal KL9010 is connected.

5

n

K-Bus error in register
communication with Bus
Terminal n

Exchange the nth bus terminal

0

Error at initialisation

Exchange Bus Coupler

1

Internal data error

Perform a hardware reset on the Bus Coupler (switch off and
on again)

6

2

DIP switch changed after a
software reset

Perform a hardware reset on the Bus Coupler (switch off and
on again)

7

0

Note: Cycle time was
exceeded

Warning: the set cycle time was exceeded. This indication
(flashing LEDs) can only be cleared by booting the Bus
Coupler again.
Remedy: increase the cycle time

0

Checksum error in Flash
program

Re-transfer the program to the Bus Terminal Controller

9

1

Incorrect or faulty library
implemented

Remove the faulty library

10

n

Bus Terminal n is not
consistent with the
configuration that existed
when the boot project was
created

Check the nth Bus Terminal. The boot project must be deleted
if the insertion of an nth bus terminal is intentional

14

n

nth Bus Terminal has the
wrong format

Start the Bus Coupler again, and if the error occurs again then
exchange the Bus Terminal

15

n

Number of Bus Terminals is
no longer correct

Start the Bus Coupler again. If the error occurs again, restore
the manufacturers setting using the KS2000 configuration
software

16

n

Length of the K-Bus data is
no longer correct

Start the Bus Coupler again. If the error occurs again, restore
the manufacturers setting using the KS2000 configuration
software

LED bus - fieldbus diagnosis

LED

Meaning

LED RUN

no fieldbus connected, Bus Coupler searches for baud rate

LED BF

error flashing - error type - display

LED DIA

Bus Coupler has found baud rate, waiting for config and parameter data

LED RUN

LED BF LED DIA

Meaning

off

off

off

no fieldbus connected, Bus Coupler searches for baud rate

on

on

on

on

on

off

Bus Coupler has found baud rate, waiting for config and parameter data

on

off

off

no error, coupler in data exchange

on

off

flashing

error, see error code