Fieldbus Components

ADS Services

Local process image task 1 port 801

Data can be read from and written to the local process image. If it is necessary for outputs to be written, it is
important to ensure that they are not used by the local PLC, because the local controller will overwrite these values.
The data is not associated with a watchdog, and therefore must not be used for outputs that would have to be
switched off in the event of a fault.

Index group

Meaning

Index offset (value range)

0xF020

Inputs

0...2047

0xF030

Outputs

0...2047

0x4020

Flags

0...4095

ADS services
AdsServerAdsState

Data type (read only)

Meaning

String

Start - the local PLC is running
Start - the local PLC is stopped

AdsServerDeviceState

Data type (read only)

Meaning

INT

0 – Start - the local PLC is running
1 – Stop - the local PLC is stopped

AdsServerType

Data type (read only)

Meaning

String

BX PLC Server

Register port 100

The ADS port number in the Bus Terminal Controller for register communication is fixed, being set at 100.

Index offset (value range)

Index group

Hi-Word

Low Word

Meaning

0 [READ ONLY]

0..127

0..255

Registers in the Bus Coupler
High word, table number of the Bus Coupler
Low word, register number of the table

1-255

0-3

1-255

Register of the Bus Terminal
High word, channel number
Low word, register number of the Bus Terminal

Note

Note when reading the register that the time out for the ADS block is set to a time longer
than 1 second.

Note

Note when writing to the registers that the password is set (see the documentation for the
particular Bus Terminal).