Selecting the target system, Downloading a bx configuration, Ads serial (all bx and bcxx50-controller) – BECKHOFF BC3150 User Manual

Page 32

Advertising
background image

Safety Instructions

30

Fieldbus Components

Downloading a BX Configuration

The configuration is transferred to the Bus Terminal Controller via ADS.

ADS serial (all BX and BCxx50-Controller)

Enter the serial ADS connection, as described in section Serial ADS.

ADS fieldbus (only BX3100, BX5100, BX9000, BC3150, BC5150)

A prerequisite is that TwinCAT operates as the master and data exchange is active, i.e. physical and PROFIBUS,
CANopen configuration must be completed, and data must be exchanged from the master (FC310x, FC510x) to the
Bus Terminal Controller.

Selecting the target system

Select the BXxx00 to which you wish to upload the configuration. F8 opens the dialog for downloading the associated
device.

Select the associated Bus Terminal Controller.

The device state (BX) is displayed at the bottom right of the System Manager.

In Config Mode / FreeRun the configuration can now be transferred to the BX. If the BX is in Stop Mode, ADS
communication has not yet been activated. In this case, the configuration cannot be downloaded.

Advertising