Power contacts supply (up), Power contacts, Power supply – BECKHOFF BC3150 User Manual

Page 21

Advertising
background image

Safety Instructions

Fieldbus Components

19

Power supply

Bus Terminal Controller and Bus Terminal supply (Us)

The Bus Terminal Controller requires a supply voltage of 24 V

DC

for its operation.

The connection is made by means of the upper spring-loaded terminals labelled 24 V and 0 V. This supply voltage
feeds the Bus Coupler / Bus Terminal Controller electronics and, over the K-Bus, the electronics of the Bus
Terminals. It is electrically separated from the potential of the field level.

UL requirements

Danger

For the compliance of the UL requirements Us should only be supplied

by a 24 V

DC

supply voltage, supplied by an isolating source and protected by

means of a fuse (in accordance with UL248), rated maximum 4 Amp.

by a 24 V

DC

power source, that has to satisfy NEC class 2.

A NEC class 2 power supply shall not be connected in series or parallel with an-
other (class 2) power source!

Danger

To meet the UL requirements, Us must not be connected to unlimited power sources!

Power contacts supply (Up)

The bottom six connections with spring-loaded terminals can be used to feed the supply for the peripherals. The
spring-loaded terminals are joined in pairs to a power contact. The feed for the power contacts has no connection to
the voltage supply for the BC electronics.

The spring-loaded terminals are designed for wires with cross-sections between 0.08 mm

2

and 2.5 mm

2

.

The assignment in pairs and the electrical connection between feed terminal contacts allows the connection wires to
be looped through to various terminal points. The current load from the power contact must not exceed 10 A for long
periods. The current carrying capacity between two spring-loaded terminals is identical to that of the connecting
wires.

Power contacts

On the right hand face of the Bus Terminal Controller there are three spring contacts for the power contact
connections. The spring contacts are hidden in slots so that they can not be accidentally touched. By attaching a Bus
Terminal the blade contacts on the left hand side of the Bus Terminal are connected to the spring contacts. The
tongue and groove guides on the top and bottom of the Bus Terminal Controllers and of the Bus Terminals
guarantees that the power contacts mate securely.