Technical Data - PROFIBUS DP

System data

PROFIBUS (BC3150)

Number of I/O modules

126 (BC3150 max. 99 devices)

Number of I/O points

depending on controller

Data transfer medium

shielded copper cable 2 x 0.25 mm², cable type A according to EN 50170

Segment length

up to 1200 m

Number of segments

3

Data transfer rate

up to 12 MBaud

Topology

RS485 line, optical fiber ring

Transmission time

approx. 0.5 ms with 10 stations for 32 bits input/output at 12 MBaud