Technical Data - PROFIBUS DP
System data
PROFIBUS (BC3150)
Number of I/O modules
126 (BC3150 max. 99 devices)
Number of I/O points
depending on controller
Data transfer medium
shielded copper cable 2 x 0.25 mm², cable type A according to EN 50170
Segment length
up to 1200 m
Number of segments
3
Data transfer rate
up to 12 MBaud
Topology
RS485 line, optical fiber ring
Transmission time
approx. 0.5 ms with 10 stations for 32 bits input/output at 12 MBaud