Product overview

The EL9080 separation terminal interrupts the power contacts within a bus terminal block. The terminal
enables operation with different voltages on the separated sides of the power contacts. But the K­Bus is
looped through. The discontinuance of the Power Contacts is especially displayed by the orange front plate
of the EL9080. The EL9080 separation terminal does not have any other function or connection facility.

Technical Data

EL9011

EL9080

Electrical isolation

yes

Bit width in the process image 0

Configuration

no address or configuration settings

Diagnosis

­

PE contact

no

Electrical connection to
mounting rail

no

Weight

approx. 8 g

approx. 40 g

Permissible ambient
temperature

­25°C ... +60°C (extended temperature range)
0°C ... +55°C (according to cULus [

}

 74] for Canada and USA)

0°C ... +55°C (according to ATEX, see special conditions)

Permissible ambient
temperature range (during
storage)

­40°C ... +85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 7 mm x 100 mm x 34 mm
(width aligned: 5 mm)

approx.15 mm x 100 mm x 70 mm
(width aligned: 12 mm)

Mounting [

}

 60]

aligned to the last terminal in the
terminal block

on 35 mm mounting rail conforms to
EN 60715

Vibration/shock resistance

conforms to EN 60068­2­6/EN 60068­2­27

EMC resistance burst/ESD

conforms to EN 61000­6­2/EN 61000­6­4

Protect. class

IP 20

Installation pos.

variable

Approval

CE
ATEX
cULus [

}

 74]

EL9xxx