14 error code 0x001b, 15 error code 0x001c – BECKHOFF EL9xxx User Manual

Page 82

Advertising
background image

Appendix

Description

If too many RxPDO Toggle error occur, i.e. the RxPDO Toggle Failed Counter increases the internal limit the
slave returns to SAFEPERROR with 0x001A. Multiple synchronization errors. Device is not synchronized any
more (used if the causes mirrored by the AL Status Codes 0x2C, 0x2D, 0x32, 0x33, 0x34 cannot be
distinguished).

Current State (or state change)

O, S→O

Resulting state

S + E

Solution

n/a

7.4.14

Error Code 0x001B

Meaning

Sync manager watchdog

Description

The slave did not receive process data within the specified watchdog time. Usually, the WD time is 100ms.
The WD is re­started every time it receives new process data, usually when the Output SyncManager
(SyncManager2) is written. For devices which have only inputs usually no WD is used. Increasing the WD is
not a solution.

Reason: PLC stopped

Current State (or state change)

O, S

Resulting state

S + E

Solution

n/a

7.4.15

Error Code 0x001C

Meaning

Invalid Sync Manager Types

Description

n/a