BECKHOFF EL9xxx User Manual

Page 47

Advertising
background image

Product overview

Technical data

Technical data

EL9540

EL9550

Function

surge filter field supply

surge filter system and field supply

Nominal voltage

24 V (­15 %/+20 %)

Surge filter field supply

yes

Surge filter system supply

­

yes

Diagnostics

­

Reported to E­Bus

­

PE contact

yes

­

Shield connection

­

Current consumption E­bus

­

Bit width in the process image 0

Connection to mounting rail

­

Electrical isolation

­

Side by side mounting on
EtherCAT Terminals with
power contact

yes

­

Side by side mounting on
EtherCAT Terminals without
power contact

yes

Dimensions (B x H x T)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Configuration

no address­ or configuration setting necessary

Weight

approx. 50 g

Permissible ambient
temperature range (during
operation)

­25°C ... +60°C (extended temperature range)
0°C ... +55°C (according to cULus [

}

 74] for Canada and USA)

0°C ... +55°C (according to ATEX [

}

 71], see special conditions [

}

 71])

Permissible ambient
temperature range (during
storage)

­40°C ... +85°C

Permissible relative humidity

95%, no condensation

Mounting [

}

 60]

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

conforms to EN 60068­2­6/EN 60068­2­27

EMC resistance burst/ESD

conforms to EN 61000­6­2/EN 61000­6­4

Protect. class

IP 20

Installation pos.

variable, see chapter "Mounting of Passive Terminals [

}

 70]"

Approval

CE
ATEX [

}

 71]

cULus [

}

 74]

LEDs and connection EL9540

LED

Color

Meaning

Power­LED

green

off

24 V

DC

 field supply not present

on

24 V

DC

 field supply present

EL9xxx

47

Version 3.1