Product overview

Technical data

Technical data

EL9200

EL9210

EL9290

Nominal voltage

24 V

DC

variable, up to 230 V AC

Power contact current load

max. 10 A

Electrical isolation

yes

Integrated fine­wire fuse

yes; 6.3 A

Current consumption from E­
Bus

­

typ. 90 mA

­

Bit width in the process image ­

1 bit (diagnosis)

­

Configuration

no address or configuration settings

Power LED

yes

yes

no

Diagnosis (fuse)

yes, Error LED

yes, in process image
and ErrorLED

no

Electrical connection to
mounting rail

no

PE contact

yes

Weight

approx. 55 g

Permissible ambient
temperature range (during
operation)

0°C ... +55°C

Permissible ambient
temperature range (during
storage)

­25°C ... +85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting [

}

 60]

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

conforms to EN 60068­2­6/EN 60068­2­27

EMC resistance burst/ESD

conforms to EN 61000­6­2/EN 61000­6­4

Protect. class

IP 20

Installation pos.

variable, see chapter
"Mounting of Passive
Terminals [

}

 70]"

variable

variable, see chapter
"Mounting of Passive
Terminals [

}

 70]"

Approval

CE
ATEX [

}

 71]

cULus [

}

 74]

CE

Connection EL9200, EL9210, EL9290

CAUTION

Hazard to individuals and devices!

When designing a Bus Terminal block with different potentials on the power contacts (e.g.
230 V AC and 24 V DC), please note that it is mandatory to use potential separation termi­
nals (EL9080)! 
Bring the bus system into a safe, powered down state before starting installation, disas­
sembly or wiring of the Bus Terminals!