BECKHOFF EL9xxx User Manual

Page 38

Advertising
background image

Product overview

Terminal point

Description

Indication

No.

+24 V* / 230 V AC**

1

Supply input + 24 V [EL9200, EL9210]
Supply input 230 V AC [EL9290: variable voltage, up to 230 V AC]
connected internally with terminal 4 and positive [EL9200, EL9210]
resp. 230 V AC [EL9290] power contact)

0 V* / N**

2

0 V for supply input [EL9200, EL9210]
N for supply input [EL9290]
connected internally with terminal 5 and negative [EL9200, EL9210]
resp. neutral [EL9290] power contact)

PE

3

PE (connected internally with terminal 6 and PE power contact)

+24 V* / 230 V AC**

4

Supply input + 24 V [EL9200, EL9210]
Supply input 230 V AC [EL9290: variable voltage, up to 230 V AC]
connected internally with terminal 1 and positive [EL9200, EL9210]
resp. 230 V AC [EL9290] power contact)

0 V* / N**

5

0 V for supply input [EL9200, EL9210]
N for supply input [EL9290]
connected internally with terminal 2 and negative [EL9200, EL9210]
resp. neutral [EL9290] power contact)

PE

6

PE (connected internally with terminal 3 and PE power contact)

* only EL9200, EL9210
** only EL9290

LEDs

LED

Color

Meaning

Power LED**

green

off

No input voltage at supply input

on

24 V

DC

 at supply input

Error LED**

red

off

Fuse OK

on

Fuse error

** only EL9200, EL9210

Process data (only EL9210)

The EL 9210 has a bit width of 2 bits (diagnosis bit for the power contacts voltage, "PowerOK" and diagnosis
bit for fuse error, "FuseError") and is displayed in the TwinCAT tree as follows:

Fig. 30: EL9210 in the TwinCAT tree

If there is no voltage impressed on the power contacts, the corresponding diagnosis bit 'PowerOK' has
FALSE (0) status.
If there is a fuse error, the corresponding diagnosis bit 'FuseError' has TRUE (1) status.

EL9xxx

38

Version 3.1

Advertising