f:\standard ioms - current release\42004 instr. manuals\42004-701l2f.doc
04/09

• A maximum of 16 Model LE200s can be connected within a single zone or Page/Party

®

subsystem

• Avoid having more than one Model LE200 connected to a particular Page/Party

®

cable. Instead, use

the LVDS link whenever possible.

• Line extenders can NOT be wired in a loop architecture for redundant connections as shown below:

Figure 15. Invalid Loop Connection of Page/Party

®

Systems

• All contact input states are ORed together to determine a contact output state.
• All remote page line audio detected states are ORed together to determine the remote page line audio

detected state used by that contact output.

• All remote page line ground fault states are ORed together to determine the remote page line ground

fault state used by that contact output.

• When enabled, 50 kHz VLC signal on any page line is transmitted to all page lines.
• SmartSeries FSK data on any page line is transmitted to all page lines.
• Manual retraining of echo cancellation at one Model LE200 also requests it at all digitally

interconnected Model LE200s.