Pump/Dispenser Manual Test
Page 52
MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005
3
Turn the AC power and battery power switches, in the pump control unit located in the upper
righthand corner of the power supply, to the ON position (up).
4
Place the system override switch for Hose 1 in the MAN (manual) position.
5
Turn on Hose 1. After completing reset, the hose should be able to dispense product.
6
Turn on all other hoses. No other hoses besides 1 should activate.
7
Turn off all hoses.
8
Place the system override switch, for Hose 1 in the ON position.
9
Repeat steps
through
for all remaining hoses. Substitute the hose number being tested for
hose 1 until all hoses have been tested.
10
Replace all connectors and reassemble.
AC power is present on the terminal blocks. Electrical shock may occur if the
operator comes in contact with these connections.
WARNING