Figure 10-2: sample tank monitor printout – Gasboy Site Controller III Start-Up User Manual
Page 85

MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005
Page 73
Communication Tests
Figure 10-1: Sample of Creating TMTST.CMD File for TLS-350
4
At the command prompt (R* or [P:]*), type TMTST and press ENTER.
Once the command has completed, you should have a printout similar to the one shown in
Figure 10-2: Sample Tank Monitor Printout
5
Once you have verified the communications are working, type DEL TMTST.* and press
ENTER.
This deletes the TMTST files.
REC TMTST.CMD <ENTER>
Data?
*TM PORT TEST <ENTER>
PORT OPEN 2 BAUD 9600 <ENTER>
PORT SEND ~01 <ENTER>
PORT SEND 200 <ENTER>
LOOP <ENTER>
PORT RECEIVE QUIET 2 FILE TMTST.DTA <ENTER>
IF ‘%E = 1 <ENTER>
RETURN <ENTER>
PORT CLOSE <ENTER>
TY TMTST.DTA <ENTER>
. <ENTER>
P:
VEEDER-ROOT
TLS
TANK LEVEL SENSOR
----------
FEB 9, 2005
2:25 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 3858 34.60 0.0 72.9 1142
2 DIESEL 7331 66.01 1.0 60.2 2669