Programming, Sa controller confi guration screens, Sa controller operator interface – Orion System SA Controller User Manual

Page 19

Advertising
background image

SA Controller Operator Interface

Programming

19

SA Controller Confi guration Screens

Confi guration Screen #6 - Dehumidifi cation

Control

SA Unit Cnfg ID 102

Dehumidification

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if your system requires Dehumidifi cation Control.

Enter

<0>

for NO. Default is NO.

Confi guration Screen #7 - Dehumidifi cation

Priority

SA Unit Cnfg ID 102

Dehumidification

Priority: NO
[0=NO 1=YES]

Enter

<1>

for YES if Dehumidifi cation is a Priority during the Occupied

Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter

<0>

for NO.

Confi guration Screen #8 - Dehumidifi cation

Unoccupied

SA Unit Cnfg ID 102

Dehumidification

Unoccupied: NO

[0=NO 1=YES]

Enter

<1>

for YES if Dehumidifi cation is required during the Unoccu-

pied mode. Unoccupied Dehumidifi cation is activated based on Indoor
Air Humidity only. Enter

<0>

for NO. Default is NO.

Confi guration Screen #9 - Entering Air

Humidity Sensor

SA Unit Cnfg ID 102

Entering Humidity

Sensor: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with an Entering Air

Humidity Sensor. Enter

<0>

for NO. Default is NO.

Confi guration Screen #10 - Indoor Air

Humidity Sensor

SA Unit Cnfg ID 102

Indoor Humidity

Sensor: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with an Indoor Air

Humidity Sensor. Enter

<0>

for NO. Default is NO.

Confi guration Screen #11 - Heat During

Dehumidify

SA Unit Cnfg ID 102

Heat During

Dehumidify: NO

[0=NO 1=YES]

Enter

<1>

for YES if your application needs to use unit heat during

Dehumidifi cation to supplement Reheat. If Reheat is not available, this
selection will allow unit heat to operate in place of Reheat. Enter

<0>

for NO. Default is NO.

Confi guration Screen #12 - Water Side

Economizer Control

SA Unit Cnfg ID 102

Water Side Economizer

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if the SA Controller is controlling the Water Side

Economizer. Enter

<0>

for NO. Default is NO.

Confi guration Screen #13 - Water Side is

Variable

SA Unit Cnfg ID 102

Water Side is

Variable: NO

[0=NO 1=YES]

Enter

<1>

for YES if the Water Side Economizer has Variable Flow.

Enter

<0>

for Constant Flow. Default is NO.

Advertising