Programming, Sa controller setpoint screens, Sa controller operator interface – Orion System SA Controller User Manual

Page 33

Advertising
background image

SA Controller Operator Interface

Programming

33

Setpoint Screen #28 - Adaptive Defrost Adj.

Setpoint

SA Unit Spts ID 102

Adaptive Defrost

Adj. Setpoint: 0 MIN

Enter a value greater than zero to enable the Adaptive Defrost Adjust-
ment of the Heat Pump Defrost Timer (Screen #27). This adjustment
value will be subtracted from the Heat Pump Defrost Timer if the Defrost
Mode lasts the entire 10 minutes. A proportion of this adjustment value
will be added to the Heat Pump Defrost Timer if the Defrost Mode only
lasts between 8 minutes and 0 minutes. This screen only applies if using
the SA Controller and a Head Pressure Module. This screen does not
appear if using the SA Controller and a WSHP Protection Module in a
Water Source Heat Pump application.

Description

Minimum

Default

Maximum

Adaptive Defrost Adj.

0 Min

0 Min

30 Min

Setpoint Screen #29 - Internal Schedule

Optimal Start Soak Multiplier

SA Unit Spts ID 102

Internal Schedule

Optimal Start Soak

Multiplier: 0.0

The Internal Schedule Optimal Start Soak Multiplier Setpoint is a multi-
plier that if set to a number greater than 0 will be used as a multiplier for
calculating the Optimal Start Time for the HVAC unit. This multiplier
is only applied if the unit has been off for more than 24 hours. See the
SA Controller Technical Guide for more detailed information regarding
the Optimal Start. This multiplier is only applied if you are using the
SA Internal Schedule.

Description

Minimum

Default

Maximum

Internal Schedule Optimal

Start Soak Multiplier

0.0

0.0

5.0

Setpoint Screen #30 - Trend Log Interval

SA Unit Spts ID 102

Trend Log

Interval: 15 MIN

An internal Trend Log is constantly updated at a rate equal to this
value.

Description

Minimum

Default

Maximum

Trend Log Interval

1 Min

15 Min

120 Min

Setpoint Screen #31 - Sensor Calibration for

SPC & SAT

SA Unit Spts ID 102

Sensor Calibration

SPC: XX.Xº 0.00º
SAT: XX.Xº 0.00º

If the Space or Supply Air Temperature Sensors are reading incorrectly,
you can use this option to enter an offset temperature to adjust the Sen-
sor’s Temperature. Enter a positive Sensor Calibration value to raise the
Space Temperature and/or Supply Air Temperature Sensor reading and
a negative value to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration SPC

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration SAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #32 - Sensor Calibration for

EAT & EWT

SA Unit Spts ID 102

Sensor Calibration

EAT: XX.Xº 0.00º
EWT: XX.Xº 0.00º

If the Entering Air or Entering Water Temperature Sensors are reading
incorrectly, you can use this option to enter an offset temperature to
adjust the Sensor’s Temperature. Enter a positive Sensor Calibration
value to raise the Entering Air or Entering Water Temperature Sensor
reading and a negative value to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration EAT

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration EWT

-100.0ºF

0.0ºF

+100.0ºF

SA Controller Setpoint Screens

Advertising