Programming, Sa controller status screens, Sa controller operator interface – Orion System SA Controller User Manual

Page 41

Advertising
background image

SA Controller Operator Interface

Programming

41

SA Controller Status Screens

Status Screen 5 - Space Temp & Slide Adjust

SA Unit v2.20 ID 102

Space Tmp.: XX.XºF
Slide Adj.: XX.XºF

Line 2 Space Temperature

If you are using a Space Temperature Sensor, this line will

display the current Space Temperature during the Occupied

or

Unoccupied

Mode.

Line 3 Slide Adjust

This is the current value of the Space Temperature offset

based on the position of the slide adjust switch on the Space

Sensor.

Status Screen 6 - Entering Air Temperature &

Entering Air Relative Humidity

SA Unit v2.20 ID 102

Entering Tmp: XX.XºF
Entering RH.: XX.X%

Line 2 Current Entering Air Temperature

If an Entering Air Temperature Sensor has been installed

and

confi gured on the unit or if an Entering Air Broadcast

has

been

confi gured on another SA Controller on the

system, the Entering Air Temperature will appear on this

line. If not, this line will display a temperature that is half

way between the Cooling and Heating Lockout Setpoints.

Line 3 Current Entering Air Relative Humidity

If an Entering Air Humidity Sensor has been installed and

confi gured on the SA Controller, the Entering Air Relative

Humidity Percentage will appear on this line. If not, this

line will display 0%.

Status Screen 7 - Entering Air Dewpoint &

Dewpoint Setpoint

SA Unit v2.20 ID 102

Entering Dp : XX.XºF
Dewpoint Spt: XX.XºF

Line 2 Current Calculated Entering Air Dewpoint
Temperature

If both an Entering Air Humidity Sensor and an Entering

Air Temperature Sensor have been installed and confi gured

on the unit, the calculated Entering Air Dewpoint

Temperature will appear on this line. If not, this screen

displays

0°F.

Line 3 Current Entering Air Dewpoint Setpoint

The user-adjustable Entering Air Dewpoint Temperature

Setpoint will appear on this line.

Status Screen 8 - Indoor RH & Indoor RH

Setpoint

SA Unit v2.20 ID 102

Indoor RH....: XXX%
Indoor RH Spt: XXX%

Line 2 Current Indoor Relative Humidity Percentage

If an Indoor Humidity Sensor has been installed and

confi gured on the unit, the current Indoor Air Relative

Humidity Percentage will appear on this line. If an Indoor

Humidity Sensor is not installed, this line will display 0%.

Line 3 Current Indoor Relative Humidity Setpoint Percentage

This is the adjustable Indoor Air Relative Humidity

Setpoint Percentage that has been set by the user.