Programming, Sa controller status screens, Sa controller operator interface 44 – Orion System SA Controller User Manual

Page 44

Advertising
background image

Zone

Zone

Programming

SA Controller Operator Interface

44

Status Screen 16 - Mod Heating %

SA Unit v2.20 ID 102

Mod Heating: XXX%

[ Optional Outputs ]

Line 2 Current Modulating Heating Output Signal
Percentage

Indicates the percentage of the output signal being

supplied to a Modulating Heating device when you have

confi gured this option for your HVAC unit. If Reverse

Acting operation is confi gured, this percentage will be

Reversed. See the following examples for clarifi cation:

Standard Operation:

0-10 VDC

0% = 0 VDC

100% = 10 VDC

2-10 VDC

0% = 2 VDC

100% = 10 VDC

Reverse

Acting

Operation:

0-10 VDC

0% = 10 VDC

100% = 0 VDC

2-10 VDC

0% = 10 VDC

100% = 2 VDC

If you do not have a Modulating Heating device confi gured,

this screen will indicate [No Mod Heat 1 Confi g].

Line 4 Indicates That These Are Optional Outputs

These outputs may or may not have live data to display.

SA Controller Status Screens

Status Screen 17 - Head Pressure Setpoint

SA Unit v2.20 ID 102

Current

Head Pr Spt: 0 PSI

Line 2-3 Current Head Pressure Cooling or Reheat Setpoint

If you are using a Two Condenser Head Pressure Module

attached to the unit, the Head Pressure Cooling or

Reheat Setpoint will display, depending on what mode the

Module is in. This status value will show 0 if not in the

Cooling

or

Dehumidifi cation Mode.

Status Screen 18 - Leaving Water Temp

SA Unit v2.20 ID 102

Leaving Water Temp

Temp A: XX.XºF
Temp B: XX.XºF

Line 2 Leaving Water Temperature

If this is a Water Source Heat Pump Unit with a Water

Source Heat Pump Protection Module, the Leaving Water

Temperature will display, depending on what mode the

Module is in. This status value will show 0 if not in the

Cooling

or

Dehumidifi cation Mode.

Line 3 Temperature A

This is the temperature of the water leaving the Water Side

Economizer

A.

Line 4 Temperature B

This is the temperature of the water leaving the Water Side

Economizer

B.

Status Screen 19 - Condenser #1

SA Unit v2.20 ID 102

Condenser #1

Head Pr.....: 0PSI
Cond Valve: 0%

Line 2 Condenser #1

If you are using the Two Condenser Head Pressure Module

attached to the unit, this line displays Condenser #1.

Line 3 Head Pressure

This line indicates the highest of the fi rst two current Head

Pressure readings on the Two Condenser Head Pressure

Module.

Line 4 Condenser Valve

This line displays the position of the associated Condenser

Valve (0-100%) that is currently necessary to maintain the

Head

Pressure

Setpoint.

Advertising