Programming, Vav/zone controller setpoint screens, Sa controller operator interface – Orion System SA Controller User Manual

Page 51

Advertising
background image

SA Controller Operator Interface

Programming

51

VAV/Zone Controller Setpoint Screens

Setpoint Screen #17 - Sensor Calibration for

Space Temp and Supply Air Temp

Sensor Calibration

SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº

[SAT Only if Sensor]

The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease
a reading.

Note: The Supply Air Temperature calibration offset only oper-

ates on the reading when the VAV/Zone Controller has
its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.

Description

Minimum

Default

Maximum

SPC (Space Temp)

-100ºF

0ºF

+100ºF

SAT (Supply Air)

-100ºF

0ºF

+100ºF

Advertising