SA Controller Operator Interface
Programming
51
VAV/Zone Controller Setpoint Screens
Setpoint Screen #17 - Sensor Calibration for
Space Temp and Supply Air Temp
Sensor Calibration
SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº
[SAT Only if Sensor]
The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease
a reading.
Note: The Supply Air Temperature calibration offset only oper-
ates on the reading when the VAV/Zone Controller has
its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.
Description
Minimum
Default
Maximum
SPC (Space Temp)
-100ºF
0ºF
+100ºF
SAT (Supply Air)
-100ºF
0ºF
+100ºF