Setpoint Screen #8 - Stage Control Window

SA Unit Spts ID 102

Stage Control Window

Cooling.........: 5ºF
Heating.........: 5ºF

When the SA Controller is in Cooling Mode, if the Supply Air Tempera-
ture drops below the Active Supply Air Temperature Setpoint minus the
Cooling Stage Control Window value, a Cooling Stage will be deacti-
vated after its Minimum Run Time. In the Heating Mode, if the Supply
Air Temperature rises above the Active Supply Air Temperature Setpoint
plus the Heating Stage Control Window value, a Heating stage will be
deactivated after its Minimum Run Time. This staging window is also
used for the coil temperature during Dehumidifi cation Mode.

Description

Minimum

Default

Maximum

Stage Control Window Cooling

1ºF

5ºF

20ºF

Stage Control Window Heating

1ºF

5ºF

20ºF

Setpoint Screen #9 - Entering Air Lockouts

SA Unit Spts ID 102

Entering Air Lockouts

Cooling......: 50ºF
Heating......: 70ºF

The SA Controller will Lockout Mechanical Heating or Cooling when
the Entering Air Temperature is above or below these Setpoints.

Description

Minimum

Default

Maximum

EA Lockouts Cooling

0ºF

50ºF

100ºF

EA Lockouts Heating

35ºF

70ºF

150ºF

Setpoint Screen #10 - Cutoff Temperature

SA Unit Spts ID 102
CutOff Temperatures

Lo SAT.......: 40ºF
Hi SAT.......: 170ºF

The SA Controller will temporarily disable Heating or Cooling if while
in Heating or Cooling Mode the Supply Air Temperature rises above
the Hi SAT Cutoff Temperature Setpoint or falls below the Lo SAT
Cutoff Temperature Setpoint. See the SA Controller Technical Guide for
detailed information on the Lo and Hi Supply Air Temperature Cutoff
sequence of operation.

Description

Minimum

Default

Maximum

Lo SAT Cutoff

0ºF

40ºF

250ºF

Hi SAT Cutoff

0ºF

170ºF

250ºF

SA Controller Setpoint Screens

Setpoint Screen #11 - Minimum Supply Fan

VFD Speed For Heating

SA Unit Spts ID 102

Minimum Supply

Fan VFD Speed

For Heating..: 30%

If the Supply Fan VFD Signal falls below the Minimum Supply Fan
VFD Speed For Heating Setpoint, Heating will be disabled.

Description

Minimum

Default

Maximum

Min Supply Fan VFD

Speed For Heating

0%

30%

100%

Setpoint Screen #12 - Morning Warm Up Temp

SA Unit Spts ID 102

Morning WarmUp

Target Temp: 72º F

Max Length.: 60 Min

When the SA Controller is confi gured for VAV operation and the con-
troller enters the Occupied Mode, the SA Controller looks at the Enter-
ing Air Temperature to determine if the unit should initiate Morning
Warm-up Mode. If the Entering Air Temperature is below the Morning
Warm-up Target Temperature and the Max Length is greater than “0,”
the SA Controller will initiate Heating. This is considered Morning
Warm-up and will run until the Entering Air Temperature rises above
the Morning Warm-up Target Temperature or until the Max Length
Setpoint time expires.

Description

Minimum

Default

Maximum

Morning Warm Up

Target Temp

50ºF

72ºF

90ºF

Morning Warm Up

Max Length

0 Min

60 Min

240 Min