Thermocouple check, Hermocouple, Heck – Super Systems 9205 Series User Manual

Page 105

Advertising
background image

Series 9205 Operations Manual Rev A

104

Example: Using quench oil as an example, suppose the SP is 200 °F. The alarm is set as a deviation of +10

°F. At 210 °F, the alarm is active and the pump will run to cool the oil. With a hysteresis of 8 °F, the alarm

and pump will turn off at 202 °F. It will turn back on when it is 10 °F above setpoint. If the setpoint is still

200 °F, then at 210 °F, it will turn on again.

Clicking on this value will display an input box from which the user can select a new value. The range is

from 0 to 9999.

Smart Alarm

This value is a display of the Smart Alarm status. A smart alarm is an alarm that works with a Process

Variable (PV), and, when enabled, it will not be active until the PV is within band of the setpoint. The alarm

sounding - if active - will be disabled until within the SP band. When it is in band, the alarm will go active

unless on delay time is set.

Example: If the SP is 1700 °F and the band is 10 °F, the alarm will not be active until the PV reaches 1690

°F. The value can be either disabled or enabled.

ON Delay Time

This value is the ON Delay Time. Clicking on this value will display an input box from which the user can

select a new value. The range is from 0 to 9999.

0 SP Blocks Alarm

This value will allow a 0 setpoint to block an alarm. The options are either no or yes.

BO/Impedance Inhibits Alarm

This option will allow the user to specify if a burnoff or impedance test will keep the alarm from sounding.

The options are either no or yes.

Inhibit Source

Alarms can be inhibited in order to prevent false or unnecessary alarm notifications. The Inhibit Source

option will allow the user to set the source of the inhibit signal. The options are: None, Input 1 – Input 4,

Soak timer inactive (The alarm will not happen if the furnace is in a soak if this option is selected), and .

Input 6 – Input 15.

Disable on Open Input

An alarm can be disabled when an input the open in order to avoid false or unnecessary alarms. This option

will allow the user to specify if the alarm is disabled when the input is open. The options are either no or

yes.

Thermocouple Check

This menu option allows the values between up to

three thermocouples to be compared to one

another. If the thermocouples go out of band, it is

possible to set up an alarm that will alert the

operators of this error.

Source 1 This assigns the first thermocouple that

will be compared. The options are:

Not used

Instrument 1-27

n/a

Input 3

Input 2

Input 1

Advertising
This manual is related to the following products: