Analog output setup – Super Systems 9205 Series User Manual

Page 52

Advertising
background image

Series 9205 Operations Manual Rev A

51

Trip Point 2 Setpoint

This is the trip point 2 setpoint value. The range is –32768 to 32767.

Trip Point 2 Force Value

This is the trip point 2 force value. The range is –32768 to 32767.

Trip Point 2 Direction

This is the trip point 2 direction. The options are: input above setpoint or input below setpoint.

High Input Limit Setpoint

This is the setpoint for the high input limit. The range is –32768 to 32767.

High Input Limit Hysteresis

This is the hysteresis for the high input limit. The range is –32768 to 32767.

Custom Curve

This will allow the user to set the custom curve to use. The curves are set up through the C

urve Entry

menu option. The options are: None, Curve 1 – Curve 3.

T/C Correction Curve

This will allow the user to set the T/C correction curve to use. The curves are set up through the

T/C

Correction Curves

menu option. The options are: None, Curve 1 – Curve 3.

The Return button will return the user to the menu screen.

Analog Output Setup

The 9205 controller has the option of six analog

outputs. The outputs are ranged for a 4 – 20 milliamp

signal or a 0 – 20 milliamp signal. Each output comes

with a factory default configuration dependent on the

application. Each output can be modified prior to

shipment to your facility or in the field by a supervisor.

Analog Output Terminals

Analog output 1 – terminals 24 and 25

Analog output 2 – terminals 25 and 26

Analog outputs 3, 4, 5, and 6 are enabled by use of an

SSi QuadDAC board that connects to two RS485

terminals on the 9205 (terminals 5 and 6 for Slave 1,

terminals 22 and 23 for Slave 2). Use the

Port Setup menu to configure communication parameters.

Assignment

The analog output assignment can be modified depending on your system requirements. To change the

Assignment first select which analog output you want to change by selecting it in the pull-down menu at the

top of the screen. The following is a list of the options:

PV 1 retrans

Loop 1 inc

Loop 1 dec

Loop 1 combo

PV 2 retrans

Loop 2 inc

Not assigned

O2 offset log

SP1 retrans

SP2 retrans

SP3 retrans

Programmer ID number

Programmer DAC 5

Programmer DAC 6

Prog 2 Quench speed (0-1000=0-100%)

Programmer 2 DAC 1

Programmer 2 DAC 2

Programmer 2 DAC 3