Series 9205 Operations Manual Rev A

165

SETOUTPT

Output Level

N/A

Output

This opcode is used to set an analog output to the specified value. The output must be assigned as a

Programmer DAC when SETDAC is called in a recipe. The Programmer DAC assignment is done in the

Analog Output Setup menu on the 9205 touch screen or in Configurator. The Analog Output Setup menu

contains Offset and Range settings, which will be proportionally applied to the 4-20mA output range.

The range for output level is -301 (disable) to 32767.

The range for output is 1 to 6.

SETPT

Temperature Setpoint

N/A

Option

This opcode is used to set the temperature set point.

The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301

(disable) – 30000.

The Option will wait for the setpoints to be reached: Blank (Don’t Wait), Wait, Wait Up, or Wait Down.

Note –

The Blank option is an actual blank line, not the word “Blank”

.

SL_PV_INQ

Process Variable

Slave

Option

This opcode will check a slave instrument for a specific process variable value, and wait until the PV from

the slave instrument matches.

The Process Variable is the PV to check. The range is -301 (disable) – 32000.

The Slave is the slave instrument to check. The range is 1 – 12.

The Option is the wait options for the opcode. The options are: Wait, Wait Up, or Wait Down.

SOAK

N/A

N/A

Soak Time

This opcode is an unconditional soak for the time (in hours and minutes) specified. The programmer will

hold for the time specified, and nothing except the operator pausing the recipe will put the program in a

hold state.

The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –

166, and the Minutes range from 0 – 59.

TC_CHK

Source 1

Source 2

Source 3

This opcode will check a TC

Source 1 will determine the first source to check. The options are: Not Used, Instrument 1 – Instrument 25,

and Input 1 – Input 3.

Source 2 will determine the second source to check. The options are: Not Used, Instrument 1 – Instrument

25, and Input 1 – Input 3.

Source 3 will determine the third source to check. The options are: Not Used, Instrument 1 – Instrument

25, and Input 1 – Input 3.

TC_INQ

Temperature Level

N/A

Option

The temperature inquiry is used to wait for the actual control temperature to reach the value specified.

The Temperature Level is the specified level to wait for. The range is -301 (disable) to 30000.

The Option is the wait options: Wait, Wait Up, or Wait Down.

The default band can be set under the Configuration Menu and is typically 15 degrees. The band limit can

be changed by the S

ET_WAIT

opcode.

The

LIMIT

opcode immediately following this opcode sets a time limit on the wait.

A

BRANCH

opcode immediately following this opcode can be used to change the program flow based on

the inquiry results.