Generic instrument setup – Super Systems 9205 Series User Manual

Page 73

Advertising
background image

Series 9205 Operations Manual Rev A

72

Generic Instrument Setup

The generic instrument’s data will be stored in certain registers

on the host instrument, such as the 9205 controller. Each

instrument is allotted a certain set of registers, starting with

register 1000. To determine the beginning register, use the

following calculation: (100 * generic instrument’s number (1 –

16)) + 900. Therefore, instrument 1 would begin at register

1000: (100 * 1) + 900. Instrument 7 would begin at register 1600:

(100 * 7) + 900. Each instrument is allotted 100 registers,

therefore, instrument 1’s allotment is from register 1000 to

1099 on the 9205 controller, instrument 2’s allotment is from

register 1100 to 1199 on the 9205 controller, etc.

The

Generic Instrument Setups

menu is split into two parts:

Coms, and Data. The screen lists the generic instruments from Instrument 1 to Instrument 16. Select the

desired instrument to configure, then choose Coms or Data.

Coms

The three reads can be set up on this screen.

Read 1 Register, Read 2 Register, Read 3 Register

The Read

X

Register field will be the register in the 9205 controller that the instrument will read from. The

range is 0 – 32767.

Read 1 Count, Read 2 Count, Read 3 Count

The Read

X

Count field will be the number of successive registers to read. The range is 0 – 100.

Read 1 Storage Offset, Read 2 Storage Offset, Read 3 Storage Offset

The Read

X

Storage Offset field will be the offset in the generic instruments registers (1000 – 1099 for

Instrument 1, 1100 to 1199 for Instrument 2, etc). The range is 0 – 100.

Data

The Process Variable (PV), Setpoint (SP), and Output (Out)

can be set up from this screen. Select the desired option

from the drop-down list to configure those settings.

Offset

The Offset field is the instrument’s register offset. The

range is 0 – 32767.

Instrument Register

The Instrument Register field is the register in the 9205

controller. The range is 0 – 32767.

Input Type

The Input Type field will determine what kind of type the

value will be. The options are: Integer, Big Endian, Big Endian Byte Swap, Little Endian, or Little Endian

Byte Swap.