background image

48

4. Next, find the wire size according to the distance between your power supply and the sign and the total

current in the following table:

Distance

Total Current (Amps)

1-20

21-40

41-60

61-80

81-100

1-15 feet

10

10

8

6

6

16-30 feet

10

8

6

4

4

31-50 feet

8

6

4

2

2

Wire Gauge (AWG)

Example:

10 High Density BRICK Sign, 16-30 feet from power supply

Determine total current = 10 Bricks × 4.8 Amps = 48 Amps(previous calculation)

From table, 16-30 feet, 41-60 Amps, results in 6-gauge wire.

Service and Maintenance

The BRICK® Sign System is designed, manufactured, and assembled to require minimum maintenance.
Because of the operating environment the BRICK system is in, some maintenance is required. The table
below lists the items in the BRICK system that require maintenance, and the recommended interval for
providing that maintenance. The recommended intervals are based on average times from previous operat-
ing systems. The intervals for your system may vary from the recommended intervals because of your
operating environment.

Note

&

&

Before performing any maintenance on the system, please read and
follow all instructions in

Important Safety Information section

For additional help regarding service and maintenance contact Technical Support or Customer Service at the
address and telephone numbers listed in Customer Service section.

Customer Service

North America customers call ALLMAND BROS., Inc. at:

Main Telephone:

800/562-1373

Fax questions to:

308/995-5887

Advertising
This manual is related to the following products: