Allmand Brothers MB 6200 User Manual

Page 49

Advertising
background image

49

Note

&

&

Items that require Maintenance:

The table below lists the items in a system that need periodic maintenance as well as the recommended
maintenance interval. A more detailed maintenance procedure for each item follows the table.

The items in the table can be used to support a BRICK system. Your
system may contain items that vary from those listed. If your system
does not contain any of the items listed, you can ignore any mainte-
nance information other than what is specifically related to the
BRICKs themselves.

Item

Maintenance Interval

(Operating Times)

Maintenance Feature

Batteries

Two weeks

One to two months

Electrolyte level; loose or corroded
terminals
Specific gravity

PV array

panels

Two weeks

PV array panel cleanliness

BRICKs

Two weeks

BRICK face contamination

Interconnect

cabling

One month

Loose or corroded connections; frayed
or broken cabling; water damage

BRICK to rail

assembly

connection

One year

Contamination and debris

Bi-Weekly

Maintain the following items bi-weekly.

PV Array Panels

Note

&

&

Warning

You can skip this maintenance requirement if your application
does not have the PV Array Panels.

The voltage and current generated by the photovoltaic (PV) arrays
and stored in the batteries on the BRICK system can cause

serious personal injury, death, or substantial equipment damage if
the correct procedures are not followed when working on the

electrical portion of the system.
Always used approved insulated tools when working on PV array
system.

Advertising
This manual is related to the following products: