SMA SB 1.5-1VL-40 User Manual

Page 51

Advertising
background image

7. Ensure that no voltage is present at the DC

inputs on the inverter using a suitable measuring
device.

8. Loosen the swivel nuts.
9. Loosen the screws of the connection cap and

remove the connection cap.

10. Use a suitable measuring device to check that no voltage is present at the AC connector

between L and N and between L and the grounding conductor. To do so, insert the test probe
(maximum diameter: 2 mm) into each round opening of the connecting terminal plate.

11. Release and disconnect the AC connector using

the sliders located on the side.

L N

1

1

2

10 Disconnecting the Inverter from Voltage Sources

SMA Solar Technology AG

Operating Manual

51

SB15-25-BE-en-10